DeviceNet Objects 125
Instance 101 - Measurement Values
This assembly instance can be selected to be sent in response to an I/O Poll
Request from a Master. This instance is the default Poll response selection for
firmware revision 3 or later, and it is the only available Poll response for
firmware revisions 1 and 2.
3
Relay 4
Status
0
Alarm 8 Status
Alarm 7 Status
4
Relay 5
Status
0
Alarm 10 Status
Alarm 9 Status
5
0
0
Alarm 12 Status
Alarm 11 Status
6
0
0
Alarm 14 Status
Alarm 13 Status
7
0
0
Alarm 16 Status
Alarm 15 Status
Table C.10 Instance 100 Data Format (Alarm and Relay Status Values Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Table C.11 Instance 101 Data Format (Measurement Values Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 - 3
Channel 1 Overall value
4 - 7
Channel 2 Overall value
8 - 11
Channel 1 Gap value (Analog Input Point (AIP) Object Instance #1)
12 - 15
Channel 2 Gap value (AIP Object Instance #2)
16 - 19
Speed value
20 - 23
Maximum Speed value
24 - 27
Channel 1 Band 1 value
28 - 31
Channel 2 Band 1 value
32 - 35
Channel 1 Band 2 value
36 - 39
Channel 2 Band 2 value
40 - 43
Channel 1 Band 3 value
44 - 47
Channel 2 Band 3 value
48 - 51
Channel 1 Band 4 value
52 - 55
Channel 2 Band 4 value
56 - 59
Channel 1 Vector 1 Magnitude value
60 - 63
Channel 1 Vector 1 Phase value
64 - 67
Channel 2 Vector 1 Magnitude value
68 - 71
Channel 2 Vector 1 Phase value
72 - 75
Channel 1 Vector 2 Magnitude value
76 - 79
Channel 1 Vector 2 Phase value
80 - 83
Channel 2 Vector 2 Magnitude value