Services – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 175
Publication GMSI10-UM013D-EN-P - May 2010
DeviceNet Objects 165
Services
12
Get
Data Format
USINT
The format of the
spectrum data.
0 = Complex data
For instances 3 and 4, this value
equals 1, which is Real data
13
Get
Average Type
USINT
The type of averaging
performed.
0 = Asynchronous (spectrum)
1 = Synchronous (waveform)
Determined by the
Synchronous attribute of the
Channel Object.
When set to Asynchronous,
consecutive spectrum
measurements are averaged
together to produce the
Spectrum data.
When set to asynchronous,
synchronized waveforms are
averaged together to produce
the Waveform data, and the
Spectrum data is produced
from the averaged waveform. A
trigger source from a
tachometer, for example, is
required to obtain the
synchronized waveforms.
14
Get/Set
Number of
Averages
UINT
The number of individual
data sets to be
incorporated into the
average calculation.
0 = Invalid
1 = No averaging
> 1 = Averaging
Table C.52 Spectrum Waveform Measurement Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
Table C.53 Spectrum Waveform Measurement Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
1
4B
h
Instance
Get_Spectrum_Chunk
Upload a portion of the
current Spectrum data.