background image

Operator Interface 3-11

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Top Level Menu

This screen (Figure 3.6) represents the main menu from which all
other screens (and the operations which they perform) are activated.
To activate an operation, simply press the function key
corresponding to the 'Softkey' shown on the screen. A screen for that
operation will be displayed. Refer to the section entitled "How To:"
for information about the various operations which may be
performed.


The screen identifies the drive product to which the operator
interface is attached and its overall state of operation. Four digital
meters show four selected parameters located in the drive. A Hobbs
meter displays the number of hours that the drive has been running.


The status of the drive will show one of the following:


NOT READY

– drive is not ready to start

READY

– drive will start when commanded

FORWARD RUN – drive is running in the forward direction

REVERSE RUN

– drive is running in the reverse direction

WARNING

– drive has a warning

FAULTED

– the drive is faulted

DISCHARGING

– waiting for input filter capacitors to

discharge on a PWM rectifier before
restart

Figure 3.6 – Top Level Menu