Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual
Page 356
![background image](/manuals/580783/356/background.png)
6-66
Component Definition and Maintenance
7000-UM150I-EN-P – June 2013
7000 “B” Frame
+15V - SPGDB TEST
3 phase, 4 wire
XXXVAC
+24V I/O
3phase
TX, XXXV/208V
XXX = 380, 480, 600
DC
FAIL
AC
FAIL
C hold-up
DC/DC
WARN
SPGDB P/S
FAIL
+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM
+12V - SCANport
+15V - TACH
6
20V
AC/DC
Converter
56 V DC
1500 W
DC/DC
FAIL
Fan
120V, single phase
Fan supply is
XXXV, 3 phase
DC/DC
Converter
Printer
Terminal
relays
20 V
Isolated
Gate Driver
Power Supply
(Optional)
+15V - SPGDB TEST
3 phase, 4 wire
XXXVAC
+24V I/O
3phase
TX, XXXV/208V
XXX = 380, 480, 600
DC
FAIL
AC
FAIL
C hold-up
DC/DC
WARN
SPGDB P/S
FAIL
+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM
+12V - SCANport
+15V - TACH
6
20V
AC/DC
Converter
56 V DC
1500 W
DC/DC
FAIL
Fan
120V, single phase
Fan supply is
XXXV, 3 phase
DC/DC
Converter
Printer
Terminal
relays
20 V
Isolated
Gate Driver
Power Supply
(Optional)
Figure 6.48 – Standard PowerFlex 7000 “B” Frame control power distribution (without UPS option)
Figure 6.49 illustrates the extended ride-through capabilities of the
control circuit. An UPS must be installed to provide the energy to
supply the AC/DC converter for an extended period of time in case
of a loss of control power. It is assumed that if control power is
interrupted, the medium voltage will also be interrupted and the drive
will not be required to operate the motor until both control and
medium voltage is re-applied.