beautypg.com

Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 438

background image

7-16

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Motor Neutral OV

67

The Neutral-to-Ground voltage measured
from the Output Filter Capacitor Neutral
point has exceeded Ground Fault

Overvoltage Trip (P189) for the duration set
in Ground Fault Overvoltage (P190). This
value is displayed in V Motor Neutral

(P347).

– Insulation Failure – Megger the motor

insulation/motor cables/drive insulation to
ground

– Verify the integrity of the output

grounding network if applicable

– Megger the input Isolation Transformer

Secondaries/Input Cables to ground

– Verify Parameter settings are appropriate

for AC Line Reactor or Isolation

Transformer drives

– Verify the integrity of Motor Filter

Capacitors, looking for short circuits or

signs of physical damage. Refer to
Chapter 6 of the User‟s Manual for
detailed instructions on Testing Filter

Capacitors.

Motor OC

21

The measured motor current I Stator (P340)
has exceeded Motor Overcurrent Trip
(P177) for the duration set in Motor
Overcurrent Delay (P178).

Possible Causes:
– Real OC/Transients
– Bad Burden resistor/Current Sensor

Circuit Failure – Check components

– Parameter settings too low compared to

torque limit – Verify Parameter settings

– Current regulator in limit (check line

voltage and Alpha line while running)

Motor OL

65

A Motor Overload condition has been
detected, where the overload condition is
calculated using I Stator(P340) and an
algorithm based on Motor Overload Trip
(P179) as the absolute trip level, Motor
Overload Delay (P180) as the base trip delay,
and Motor Overload Min (P351) as the point

where the overload calculation begins.

– Transient Loading - Check torque limit

and overload settings and Compare
loading to torque settings and trip
settings

– Burden Resistor – Check LEM feedback

and Check the burden resistors

Motor OV

22

The measured Motor AC Voltage has
exceeded Motor Overvoltage Trip (P181) for
the duration set in Motor Overvoltage Delay
(P182).

Possible Causes:
– Parameter setting incorrect (flux

command/trip values)

– VSB damage – Check VSB resistors,

grounds, and verify tap settings are

correct

– Self-Excitation – Check for flying

start/induced motor rotation