2-30
Drive Installation
7000-UM150I-EN-P – June 2013
7000 “B” Frame
Power Wiring Selection (cont.)
Cable Insulation
The cable insulation requirements for the PowerFlex 7000 drive are
given in the tables below.
A T T E N T I O N
A T T E N T I O N
Voltage ratings shown in the following
tables are peak line to ground. Some cable
manufacturers rate voltage line to line RMS.
Ensure the cable meets the rating specified
in the following tables.
Cable Insulation Requirements for 6P / PWM Drives with Line Reactor
System Voltage (V, RMS)
Cable Insulation Rating (kV)
(Maximum Peak Line to Ground)
Line Side
Machine Side
2400
2.2
4.1
3000
2.75
5.12
3300
3.0
5.63
4160
3.8
7.1
6000
5.5
10.8
6300
5.8
11.4
6600
6.0
11.8
Cable Insulation Requirements for 18P and 6P / PWM Drives with Isolation
Transformer
System Voltage (V, RMS)
Cable Insulation Rating (kV)
(Maximum Peak Line to Ground)
Line Side
Machine Side
2400
4.1
2.2
3000
5.12
2.75
3300
5.63
3.0
4160
7.1
3.8
6000
10.8
5.5
6300
11.4
5.8
6600
11.8
6.0
Cable Insulation Requirements for “Direct-to-Drive” Technology
System Voltage (V, RMS)
Cable Insulation Rating (kV)
(Maximum Peak Line to Ground)
Line Side
Machine Side
2400
2.2
2.2
3000
2.75
2.75
3300
3.0
3.0
4160
3.8
3.8
6000
5.5
5.5
6300
5.8
5.8
6600
6.0
6.0