Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual
Page 445
![background image](/manuals/580783/445/background.png)
Troubleshooting
7-23
7000 “B” Frame
7000-UM150I-EN-P – June 2013
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
U1A Fbk FO Loss
93
INVERTER SGCT FAULT
(Feedback Fiber-Optic Loss)
This fault will only occur during the initial
contactor closure and the diagnostic
sequence after a start command. The
inverter monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. This fault occurs when the feedback
was low from the device before gating, and
is still low from the device after gating. The
drive then assumes the feedback must be
the problem.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next
action
– Check that the fiber optic cables are
seated properly in the Optical Interface
Board and the SCGT firing card
– Check that the fiber optic cable is not
pinched or damaged
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify the associated 20V power supply
is powered and active
– Verify all the power connections to the
SCGT firing card are seated properly
U1B Fbk FO Loss
99
U1C Fbk FO Loss
468
U4A Fbk FO Loss
96
U4B Fbk FO Loss
102
U4C Fbk FO Loss
471
V3A Fbk FO Loss
95
V3B Fbk FO Loss
101
V3C Fbk FO Loss
470
V6A Fbk FO Loss
98
V6B Fbk FO Loss
104
V6C Fbk FO Loss
473
W2A Fbk FO Loss
94
W2B Fbk FO Loss
100
W2C Fbk FO Loss
469
W5A Fbk FO Loss
97
W5B Fbk FO Loss
103
W5C Fbk FO Loss
472
U1A Gat FO Loss
105
INVERTER SGCT FAULT
(Gating Fiber-Optic Loss)
This fault will only occur during the initial
contactor closure and the diagnostic
sequence after a start command. The
inverter monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. This fault occurs when the feedback
was high from the device before gating, and
is still high from the device after gating. The
drive then assumes the gating pulse must
not have reached the device.
The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next
action
– Check that the fiber optic cables are
seated properly in the Optical Interface
Board and the SCGT firing card
– Check that the fiber optic cable is not
pinched or damaged
– Complete a resistance check per the
instructions in the manual
– NOTE: SGCTs may not have completely
shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed
– Check the LED status of the SCGT gate
driver card for abnormal readings
– Complete a Gating Test mode check on
the devices
– Verify the associated 20V power supply
is powered and active
– Verify all the power connections to the
SCGT firing card are seated properly
U1B Gat FO Loss
111
U1C Gat FO Loss
474
U4A Gat FO Loss
108
U4B Gat FO Loss
114
U4C Gat FO Loss
477
V3A Gat FO Loss
107
V3B Gat FO Loss
113
V3C Gat FO Loss
476
V6A Gat FO Loss
110
V6B Gat FO Loss
116
V6C Gat FO Loss
479
W2A Gat FO Loss
106
W2B Gat FO Loss
112
W2C Gat FO Loss
475
W5A Gat FO Loss
109
W5B Gat FO Loss
115
W5C Gat FO Loss
478