Annual maintenance (cont.) – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual
Page 418
![background image](/manuals/580783/418/background.png)
6-128
Component Definition and Maintenance
7000-UM150I-EN-P – June 2013
7000 “B” Frame
Check for any visual/physical evidence of damage and/or
degradation of components in the low voltage compartments.
This includes Relays, Contactors, Timers, Terminal connectors,
Circuit breakers, Ribbon cables, Control Wires, etc.; Causes
could be corrosion, excessive temperature, or contamination.
Clean all contaminated components using a vacuum cleaner (DO
NOT use a blower), and wipe clean components where appropriate.
Check for any visual/physical evidence of damage and/or
degradation of components in the medium voltage compartments
(inverter/rectifier, cabling, DC Link, contactor, load break, harmonic
filter, etc).
This includes main cooling fan, power devices, heatsinks, circuit
boards, insulators, cables, capacitors, resistors, current
transformers, potential transformers, fuses, wiring, etc.; Causes
could be corrosion, excessive temperature, or contamination.
Verify that torque on heatsink bolts (electrical connections to
bullet assemblies) is within specifications (13.5 N-m).
Clean all contaminated components using a vacuum cleaner (DO
NOT use a blower), and wipe clean components where appropriate.
NOTE: An important component to check for contamination is
the heatsink. The fine grooves in the aluminum heatsinks can
capture dust and debris.
Carry out the physical inspection and verification for the
proper operation of the contactor/isolator interlocks, and
door interlocks.
Carry out the physical inspection and verification for the proper
operation of the key interlocks.
Physical verification of the additional cooling fans mounted in
the AC Line Reactor cabinet, Harmonic Filter cabinet for
mounting and connections.
Carry out the cleaning of the fans and ensure that the ventilation
passages are not blocked and the impellers are freely rotating
without any obstruction.
Carry out the insulation meggering of the drive, motor, isolation
transformer/line reactor, and the associated cabling.
Refer to User Manual, Appendix D – Meggering, for meggering
procedure.
Check clamp head indicator washers for proper clamp pressure,
and adjust as necessary.
Refer to User Manual, Chapter 6 – Component Definition
and Maintenance for details on proper clamp pressure.
Annual Maintenance
(cont.)