Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual
Page 122

Operator Interface 3-43
7000 “B” Frame
7000-UM150I-EN-P – June 2013
To modify the text attached to a particular fault input, use the [cursor
up] and [cursor down] keys to select the desired input. To modify
the text, press the [cursor right] key. (If nothing happens then you
have not gained the required access to make changes. Exit to the
SETUP screen and refer to the section entitled Enter/Modify an
Access Level to gain access). The first character position of the
string will be in reverse video as shown in Figure 3.58. Refer to the
section entitled "Edit Text". When editing is complete, the screen
will appear as in Figure 3.59.
Figure 3.58 – Modify Text
Figure 3.59 – Modification Completed
The changes made do not take affect until you press [F10] and exit
the screen. Any time prior to this you may cancel all of the changes
made after coming to the screen by pressing the [F7] key.
PLC
The drive can be optionally connected to a PLC via a RIO (Remote
Input/Output) adapter. The drive appears to the PLC as a rack of
information. The tags that are associated with each of the words
within a rack can be defined. To setup the PLC link, use the
up/down arrow keys on the SETUP screen to select the 'PLC' option
and press the [enter] key.
This will display a screen as shown in Figure 3.60 or 3.61. The PLC
setup consists of eight words of input and eight words of output.