Input, Status, Output and Configuration Files using ControlNet

Range Selection Bits for the 1793-IE2XOE1and -IE2XOE1S Analog Combo Module

Output Word/Bit Descriptions for the 1793-IE2XOE1and -IE2XOE1S Analog Combo
Module

Words 2

and 3

Reserved

Word 4

Bits 00-01

Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1.
When set (1), indicates either a broken or open input wire, or input current at
or below 4mA.

Bits 02-03

Reserved

Bits 04

Wire Off bits (W) – Current outputs only – When set (1), the wire on the
current output is broken or the load resistance is too high. Bit 00 corresponds
to channel 0.

Bits 05-14

(05-16)

Reserved

Bit 15 (17)

Power Up bit - This bit is set to 1 when all bits in the configuration
register (write word 3) are 0 (unconfigured state).
The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.

Input
Word

Decimal Bit

(Octal Bit)

Definition

Channel No.

Input

Channel 0

Input

Channel 1

Output

Channel 0

F0

C0

F1

C1

F4

C4

Decimal Bits

(Octal Bits)

00

08

(10)

01

09

(11)

04

12

(14)

4-20mA

0

1

0

1

0

1

0-10V dc/0-20mA

1

0

1

0

1

0

–10 to +10V dc

1

1

1

1

1

1

Off

1

0

0

0

0

0

0

C = Configure select bit
F = Full range bit

1

When configured to off, individual channels will return 0000H.

Output

Word

Decimal Bit

(Octal Bit)

Definition

Write

Word 0

Bits 00-14

(00-16)

Channel 0 analog data – 12-bit left justified two’s complement number; unused
lower bits are zero; 4-20mA uses all 16 bits.

Bits 15

(17)

Channel 0 analog data sign bit.