Rockwell Automation 1793-OE2S FLEX INTEGRA ANALOG MOD User Manual
Page 61

Publication 1793-6.5.1 - April 1999
6-10
Input, Status, Output and Configuration Files using ControlNet
Range Selection Bits for the 1793-IE2XOE1and -IE2XOE1S Analog Combo Module
Output Word/Bit Descriptions for the 1793-IE2XOE1and -IE2XOE1S Analog Combo
Module
Words 2
and 3
Reserved
Word 4
Bits 00-01
Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1.
When set (1), indicates either a broken or open input wire, or input current at
or below 4mA.
Bits 02-03
Reserved
Bits 04
Wire Off bits (W) – Current outputs only – When set (1), the wire on the
current output is broken or the load resistance is too high. Bit 00 corresponds
to channel 0.
Bits 05-14
(05-16)
Reserved
Bit 15 (17)
Power Up bit - This bit is set to 1 when all bits in the configuration
register (write word 3) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.
Input
Word
Decimal Bit
(Octal Bit)
Definition
Channel No.
Input
Channel 0
Input
Channel 1
Output
Channel 0
F0
C0
F1
C1
F4
C4
Decimal Bits
(Octal Bits)
00
08
(10)
01
09
(11)
04
12
(14)
4-20mA
0
1
0
1
0
1
0-10V dc/0-20mA
1
0
1
0
1
0
–10 to +10V dc
1
1
1
1
1
1
Off
1
0
0
0
0
0
0
C = Configure select bit
F = Full range bit
1
When configured to off, individual channels will return 0000H.
Output
Word
Decimal Bit
(Octal Bit)
Definition
Write
Word 0
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number; unused
lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
(17)
Channel 0 analog data sign bit.