Input, Status, Output and Configuration Files using ControlNet

6-7

Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module

Configuration Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input
Module

2 Output Analog Module (Cat. No. 1793-OE2 and -OE2S)

Channel No.

Channel 0

Channel 1

Channel 2

Channel 3

F0

C0

F1

C1

F2

C2

F3

C3

Decimal Bits

(Octal Bits)

00

08

(10)

01

09

(11)

02

10

(12)

03

11

(13)

0-10V dc/0-20mA

1

0

1

0

1

0

1

0

4-20mA

0

1

0

1

0

1

0

1

–10 to +10V dc

1

1

1

1

1

1

1

1

Off

1

0

0

0

0

0

0

0

0

C = Configure select bit
F = Full range bit

1

When configured to off, individual channels will return 0000H .

Configuration

Word

Decimal Bit (Octal Bit)

Definition

Write Word 0

Bits 00-03

Full range bits (F) for individual channels – Bit 00 corresponds to input channel
0, bit 01 corresponds to input channel 1, and so on.

Bits 04-07

Reserved

Bits 08-11 (10-13)

Configure select bits (C) for individual channels – Bit 08 corresponds to input
channel 0, bit 09 corresponds to input channel 1, and so on. Refer to Range Bit
Selections.

Bits 12-15 (14-17)

Reserved

Module Image

ControlNet Files

Analog Data Channel 0

Analog Data Channel 1

Not used

Not used

Not used

Not used

Diagnostics

Config. Select

Full Range

Input File Size

Output File Size

0 or 1 Word

0 to 4 Words

Read

Write

M

PU

Reserved

Reserved

Configuration File Size

1 to 2 Words

Write