How to Install Your Analog Module

2-5

Connecting Wiring for the
Analog Modules

Connecting Wiring for the 1793-IE4 Input Module

This module is available with 2 styles of connectors; screw-cage and spring
clamp. Refer to the wiring figure below.

1. Connect individual analog channel signal wiring to terminals on row A

and row C. Use Belden 8761 cable for signal wiring..

2. Connect the associated channel common to common terminals 1, 6, 9 or

14 according to the wiring table on the next page.

3. Connect +24V dc to terminal 8 on row B.

4. Connect 24V dc common to terminal 0 on row A.

5. If daisy-chaining +24V dc from this module to the next FLEX Integra

module, connect a jumper from terminal 15 to terminal 8 on the next
FLEX Integra module.

6. If daisy-chaining 24V dc common from this module to the next FLEX

Integra module, connect a jumper from terminal 7 on this module to
terminal 0 on the next Integra module.

ATTENTION: Connect only 1 current or 1
voltage signal per channel. Do not connect both
current and voltage on 1 channel.

1793-IE4

1793-IE4S

0

1

2

3

4

5

6

7

8

9

10

11

A

B

13

14

15

12

41470

C

C

C

C

V

V

C

C

I1

I0 V0

V1

I3

I2

V2

V3

Ch 0

Ch 1

Ch 2

Ch 3

0

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15

A

B

41471

C

C

V

V

C

C

V

1

V

2

I

2

I

1

V

3

V

4

I

4

I

3

C

C

Ch 0 Ch 1

Ch 2 Ch 3

Where: C = 24V dc common, V = 24V dc power, I

n

= current in, V

n

= voltage in