Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
4-9
Analog Combo Module (1793-IE2XOE1 and -IE2XOE1S) Write Configuration Block
Word 4
Bits 00-01
Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1.
When set (1), indicates either a broken or open input wire, or input current at
or below 4mA.
Bits 02-03
Reserved
Bits 04
Wire Off bits (W) – Current outputs only – When set (1), the wire on the
current output is broken or the load resistance is too high. Bit 00 corresponds
to channel 0.
Bits 05-14
(05-16)
Reserved
Bit 15 (17)
Power Up bit - This bit is set to 1 when all bits in the configuration
register (write word 3) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.
Word
Decimal Bit
(Octal Bit)
Definition
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Write Word 0
S
Analog Data – Output Channel 0
Word 1
S
Reserved
Word 2
0
Not used – set to 0
M0
Word 3
Not used
C5
C4
C3
C2
C1
C0
0
0
0
F4
0
0
F1
F0
Words 4 and 5
Not used – set to 0
Word 6
S
Safe State Value – Output Channel 0
Word 7
S
Reserved
Where: M = Multiplex control bits
S = Sign bit (in 2’s complement)
C = Configure select bit
F = Full range bit