Publication 1793-6.5.1 - April 1999
2-6
How to Install Your Analog Module
Table 2.A Wiring connections for the 1793-IE4 Analog Module
Connecting Wiring for the 1793-OE2 Output Module
. This module is available with 2 styles of connectors; 1793-OE2 -
screw-cage and 1793-OE2S - spring clamp. Refer to the figure below.
1. Connect individual analog output channel signal wiring as follows:
Channel 0 - Current output - connect output signal to terminal 2
(current output) on row A. Connect the associated channel common
to terminal 1 on row A.
Channel 0 - voltage output - connect output signal to terminal 3
(current output) on row A. Connect the associated channel common
to terminal 1 on row A.
Channel 1 - Current output - connect output signal to terminal 4
(current output) on row A. Connect the associated channel common
to terminal 6 on row A.
Channel 0 - voltage output - connect output signal to terminal 5
(current output) on row A. Connect the associated channel common
to terminal 6 on row A.
1RWH 8VH %HOGHQ FDEOH IRU VLJQDO ZLULQJ
Channel
Signal Type
Label
Markings
Signal
Return
0
Current
I
2
1
Voltage
V
3
1
1
Current
I
4
6
Voltage
V
5
3
2
Current
I
10
9
Voltage
V
11
9
3
Current
I
12
14
Voltage
V
13
14
24V dc Common
Terminals 0, 1, 6, 9, and 14 are connected together in
the module.
+24V dc power
Terminals 8 and 15 are internally connected in the
module.
1793-OE4
1793-OE4S
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
A
B
41359
C
C
C
V
V
C
V
0
I
0
V
1
I
1
Ch0 Ch1
C
C
0
1
2
3
4
5
6
7
8
9
10
11
A
B
13
14
15
12
Out Ch 0 Out Ch 1
41358
I
1
V
1
Io Vo
C
V
C
C
C
V
C
C
Where: C = common; V = +24V dc power;
I = current output; V = voltage output