Rockwell Automation 1793-OE2S FLEX INTEGRA ANALOG MOD User Manual
Page 57
Publication 1793-6.5.1 - April 1999
6-6
Input, Status, Output and Configuration Files using ControlNet
4 Input Analog Module (Cat. No. 1793-IE4 and -IE4S)
Input Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module
Module Image
ControlNet Files
Input Data Channel 0
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Underrange
Configure select
Input File Size
Configuration File Size
0 or 6 Words
1 to 9 Words
PU
Reserved
Reserved
Reserved
Reserved
4-01CN
Input Word
Decimal Bit
(Octal Bit)
Definition
Input Word 0
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17)
Channel 0 analog data sign bit.
Word 1
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17)
Channel 1 analog data sign bit.
Word 2
Bits 00-14
(00-16)
Channel 2 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17)
Channel 2 analog data sign bit.
Word 3
Bits 00-14
(00-16)
Channel 3 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17)
Channel 3 analog data sign bit.
Words 4-7
Reserved
Word 8
Bits 00-03
Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1,
and so on. When set (1), indicates either a broken or open input wire, or input
current at or below 4mA.
Bits 04-14
(04-16)
Not used – set to 0.
Bit 15 (17)
Power Up bit .- This bit is set to 1 when all bits in the configuration
register (write word 0) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.