Rockwell Automation 1793-OE2S FLEX INTEGRA ANALOG MOD User Manual
Page 44
![background image](/manuals/579724/44/background.png)
Publication 1793-6.5.1 - April 1999
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
5-5
Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module Write
Channel No.
Channel 0
Channel 1
Channel 2
Channel 3
F0
C0
F1
C1
F2
C2
F3
C3
Decimal Bits
(Octal Bits)
00
08
(10)
01
09
(11)
02
10
(12)
03
11
(13)
0-10V dc/0-20mA
1
0
1
0
1
0
1
0
4-20mA
0
1
0
1
0
1
0
1
–10 to +10V dc
1
1
1
1
1
1
1
1
Off
1
0
0
0
0
0
0
0
0
C = Configure select bit
F = Full range bit
1
When configured to off, individual channels will return 0000H on Series B modules, and 4
to 20mA on Series A modules.
Word
Decimal Bit (Octal Bit)
Definition
Write
Word 1
Bits 00-03
Full range bits (F) for individual channels – Bit 00 corresponds to input channel
0, bit 01 corresponds to input channel 1, and so on.
Bits 04-07
Reserved
Bits 08-11 (10-13)
Configure select bits (C) for individual channels – Bit 08 corresponds to input
channel 0, bit 09 corresponds to input channel 1, and so on. Refer to Range Bit
Selections.
Bits 12-15 (14-17)
Reserved
2
Bits 01-15 (01-17)
Reserved
3
Bits 01-15 (01-17)
Reserved
4
Bits 01-15 (01-17)
Reserved
5
Bits 01-15 (01-17)
Reserved
6
Bits 01-15 (01-17)
Reserved