Rockwell Automation 1793-OE2S FLEX INTEGRA ANALOG MOD User Manual
Page 20
![background image](/manuals/579724/20/background.png)
Publication 1793-6.5.1 - April 1999
2-8
How to Install Your Analog Module
Table 2.B
Wiring connections for the 1793-OE2 Analog Module
Connecting Wiring for the 1793-IE2XOE1 Input/Output Module
This module is available with 2 styles of connectors; screw-cage and spring
clamp. Refer to the wiring figure below.
1. Connect individual analog input channel signal wiring to terminals on
row A. Use terminals 2 (channel 0) and 4 (channel 1) for current and
terminals 3 and 5 for current. Use Belden 8761 cable for signal wiring..
2. Connect the associated channel common to common terminals 1 and 6
according to the wiring table on the next page.
3. Connect individual analog output channel signal wiring to terminals 10
or 11 on row B. (Use terminal 10 for current, or terminal 11 for voltage -
not both.)
4. Connect the associated channel common to common terminal 9
according to the wiring table on the next page.
Channel
Type
Label Marking
Signal
Return
0
Current Signal
I
2
Current Common
RET
1
Voltage Signal
V
3
Voltage Common
RET
1
1
Current Signal
I
4
Current Common
RET
6
Voltage Signal
V
5
Voltage Common
RET
6
24V dc Common
Terminals 0, 1, 6, 7, 9 and 14
+24V dc
Terminals 8 and 15 are internally connected to +V.
$77(17,21 &RQQHFW RQO\ FXUUHQW RU YROWDJH VLJQDO
SHU FKDQQHO 'R QRW FRQQHFW ERWK FXUUHQW DQG YROWDJH RQ
FKDQQHO
1793-IE2XOE1
1793-IE2XOE1S
0
1
2
3
4
5
6
7
8
9
10
11
A
B
13
14
15
12
41473
C
C
C
C
V
V
C
C
V
0
V
1
I
1
I
0
V
o
I
o
In Ch 0
In Ch 1
Out Ch 0
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
A
B
41472
C
C
V
V
C
C
V
0
V
1
I
1
I
0
V
o
I
o
C
C
I
In Ch 0In Ch 1
Out Ch 0
V
0,1
= voltage in; I
o
= current out; V
o
= voltage out
Where: C = common; V = +24V dc power; I
0,1