Rockwell Automation 1793-OE2S FLEX INTEGRA ANALOG MOD User Manual
Page 36
Publication 1793-6.5.1 - April 1999
4-8
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
2 Input/1 Output Analog Combo Module (Cat. No. 1793-IE2XOE1 and -IE2XOE1S)
Analog Combo Module (1793-IE4XOE1) Read
Word/Bit Descriptions for the 1794-IE4XOE1 and -IE2XOE1S Analog Combo
Module Read
Words 12-13
Bits 00-15
(00-17)
Reserved
Word
Decimal Bit
(Octal Bit)
Definition
Module Image
I/O Image
Input Data Channel 0
Input Data Channel 1
Output Data Channel 0
Underrange & Diag.
Output Channel 0 Safe State
Not used
Not used
Full Range and Configure Select
Not used
Input Size
Output Size
0 to 7 Words
0 to 5 Words
Read
Write
M
PU
Not used
Reserved
Reserved
Reserved
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Word 0
S
Analog Value Input Channel 0
Word 1
S
Analog Value Input Channel 1
Word 2
S
Word 3
S
Word 4
PU
Not used – set to 0
W1
W0
Where: S = sign bit (in 2’s complement)
W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.)
PU = Power up bit
Word
Decimal Bit
(Octal Bit)
Definition
Read
Word 0
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17)
Channel 0 analog data sign bit.
Word 1
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17)
Channel 1 analog data sign bit.
Words 2
and 3
Reserved