Configure the ControlNet Network

Chapter 5

8. In the Network Parameters tab, enter the parameters that are appropriate

for your system.

9. Click OK.

10. From the Network menu, choose Single Pass Browse.
11. From the File menu, choose Save.
12. Type a name for the file that stores the network configuration, then

click Save.

13. Click Optimize and re-write Schedule for all Connections (default) and

click OK.

You have finished scheduling your new ControlNet network.

Parameter

Specify

Network Update Time (ms)

The minimum repetitive interval when data is sent over the ControlNet

network.

Max Scheduled Address

The highest node number that uses scheduled communication on the

network.

Max Unscheduled Address

The highest node number that you use on the network.

Media Redundancy

The ControlNet channels you are using.

Network Name

A name for identifying the ControlNet network.