Program the Redundant Controller

Chapter 7

Store a Project While the Controller is in Program or Remote Program
Mode

If you want to store your controller project in nonvolatile memory while your

redundant system is not running, complete these steps. Before you begin, verify

that a controller communication path has been specified and that you are able to

go online with the primary controller.

1. Verify that the redundant chassis are synchronized. If they are not

synchronized, synchronize them.

2. Use RSLogix 5000 software or the mode switch to put the primary

controller into Program or Remote Program mode.

3. In RSLinx Classic communication software, right-click the 1756-RM

module and choose Module Configuration to open the RMCT.

4. In the Configuration tab, set the Auto-Synchronization parameter to

Conditional.