Configure the Redundancy Modules

Clicking the Lock for Update command initiates the locking process. The lock

can take several minutes to finish. Monitor the System Update Lock Attempts log

to determine when the lock is complete. In addition, the chassis status shown at

the bottom-left of the dialog box changes from Primary with Disqualified

Secondary to Primary Locked for Update.

Figure 31 - Lock for Update Status Updates

Abort System Lock

The Abort System Lock command can be used to stop the system lock. It is

available as soon as a lock for update is initiated.

Clicking Abort System Lock returns the redundant chassis status to Primary with

Disqualified Secondary. Clicking Abort System Lock also results in the system

update stopping and the program in the secondary controller being cleared. If you

click Abort System Lock, you need to download the program to the secondary

controller before re-attempting a Lock for Update.

Lock initiated.

Lock complete.

Lock complete.