Redundancy Object Attributes

Appendix E

In a pair of redundant chassis,

identification of a specific chassis

without regard to the state of the

chassis.

PhysicalChassisID

INT

GSV

If

Then

0

Unknown

1

Chassis A

2

Chassis B

Slot number of the 1756-RM module

in this chassis.

1756-RM SlotNumber

INT

GSV

Size of the last crossload.

Size of the last crossload if you

had a secondary chassis.

LastDataTransfer Size

DINT

GSV

This attribute gives the size of data that was or would have been crossloaded in the

last scan in the number of DINT’s (4-byte words).
The secondary chassis does not have to be connected or online. If you do not have a

secondary chassis, the number of DINT’s that would have been crossloaded are

indicated.

Size of the biggest crossload.

Size of the biggest crossload if you

had a secondary chassis.

MaxDataTransfer Size

DINT

GSV
SSV

This attribute gives the biggest size of the LastDataTransfer Size attribute in DINTs

(4-byte words).
The secondary chassis does not have to be connected or online. If you do not have a

secondary chassis, the largest number of DINTs that would have been crossloaded

are indicated.
If you need to reset this value, use an SSV instruction with a Source value of 0.

For this information

Get this attribute

Data

Type

GSV/SSV

Description