Plan for communication module connections – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 33

background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

33

Design an Enhanced Redundancy System

Chapter 2

Plan for Communication Module Connections

A CIP connection is a point-to-point communication mechanism used to

transfer data between a producer and a consumer. These are examples of CIP

connections:

Logix5000 controller message transfer to Logix5000 controller

I/O or produced tag

Program upload

RSLinx DDE/OPC client

PanelView™ polling of a Logix5000 controller

ControlLogix ControlNet communication modules provide 131 total CIP

connections. Consider these points when using CIP connections with

ControlLogix ControlNet communication modules:

Three of the 131 CIP connections are reserved for redundancy. The three

redundant-system CIP connections always appear to be in use, even when

no connections are open.

You can use the remaining 128 CIP connections in any manner that your

application requires, such as the examples listed above.

ControlLogix EtherNet/IP communication modules provide 259 total CIP

connections. Consider these points when using CIP connections with

ControlLogix EtherNet/IP communication modules:

Three of the 259 CIP connections are reserved for redundancy.

You can use the remaining 256 connections in any manner that your

application requires, such as the examples listed above.