App a - status indicators, Status indicators, Redundancy module status indicators – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 227: 1756-rm2/a and 1756-rm2xt status indicators, Module status display, Table 40 - module status display, Appendix a, Status, P r i m, Appendix

background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

227

Appendix

A

Status Indicators

Redundancy Module Status

Indicators

The redundancy modules have these diagnostic status indicators.

1756-RM2/A and 1756-RM2XT Status Indicators

Figure 67 - Redundancy Module Status Indicators for 1756-RM2/A and 1756-RM2XT Modules

Module Status Display

The module status display provides diagnostic information.

Topic

Page

Redundancy Module Status Indicators

227

Table 40 - Module Status Display

Module Status Display

Description
Four-character display executing self-test at powerup.
No action necessary.

Txxx

The redundancy module is executing a self-test at powerup. (xxx represents a

hexadecimal test identification number.)
Wait for self-test to finish. No action required.

XFER

Application firmware update is in progress.
Wait for firmware update to finish. No action is required.

ERAS

Boot mode - Erasing current redundancy module firmware

PROG

Flash b mode - Updating redundancy module firmware
Wait for firmware update to finish. No action is required.

????

Resolving initial redundancy module state
Wait for state resolution to finish. No action is required.

CH2 CH1 OK

CH2 CH1 OK

P R I M