Configurable channel parameter list, Assembly structure – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 91

Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-61
Instance 55 Attribute (Snapshot 1 parameter record)
Assembly Structure
Configurable channel parameter list
Attribute
ID
Access
Rule
Name
DeviceNet
Data Type
3
Get
Data
Structure of
28 bytes; 14 words
Note: this table is only supported when master module
firmware is V3.00 or later
Param
#
Parameter name
Data
Type
# bytes
Description
Word
No.
1
The value of user selected parameter #1
Refer to parameter 9, Instance 23.
Float
4
Range depends on the selected parameter
1
2
2
Record Timestamp; Year
Int
8
Year
3
Record Timestamp; Month, Day
Int
Month = Value/256
Day = Remainder of Value/256
4
Record Timestamp; Hour, Minute
Int
Hour = Value/256
Minute = Remainder of Value/256
5
Record Timestamp; Seconds, hSeconds
Int
Seconds = Value/256
Hseconds = Remainder of Value/256
6
3
Snashot record # being returned
Int
2
Range 1 to 1861
7
4
Unused
Int
2
0
8
Param # Parameter name
Data type #bytes
Comment
0
None
Int
2
If this parameter is selected, a fixed 0 integer is returned
1
Relay #1 status
Int
2
See Instance 1, parameter 1
2
Relay #2 status
Int
2
See Instance 1, parameter 2
3
Alarm word
Int
2
See Instance 1, parameter 3
4
Status inputs
Int
2
See Instance 1, parameter 4
5
Voltage mode
Int
2
See Instance 6, parameter 3
6
Vaux voltage mode
Int
2
See Instance 6, parameter 4
7
L1/L1/L3 PT primary
Float
4
See Instance 6, parameter 5
8
L1/L2/L3 PT secondary
Float
4
See Instance 6, parameter 6
9
I1/I2/I3 CT primary
Float
4
See Instance 6, parameter 7
10
I1/I2/I3 CT secondary
Float
4
See Instance 6, parameter 8
11
I4 CT primary
Float
4
See Instance 6, parameter 9
12
I4 CT secondary
Float
4
See Instance 6, parameter 10
13
Vaux PT primary
Float
4
See Instance 6, parameter 11
14
Vaux PT secondary
Float
4
See Instance 6, parameter 12