Common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 123
Publication 1403-IN054B-EN-P - August 2001
DeviceNet Data Tables B-93
Common Services
Instance 3 Attributes (General Explicit Server Message
Connection)
Service Code
Implemented for:
Service Name
Class
Instance
0x05
Yes
Yes
Reset
(1)
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
(1) For "Class", resets all connections to non-existent. For "Instance", resets connection timer, and if applicable changes the state from timed out to
established.
Attribute ID
Access Rule
Name
DeviceNet
Data Value
1
Get
State
USINT
0=nonexistent
1=configuring (default)
2=waiting for connection
ID 3=established 4=timed
out 5=deferred delete
2
Get
Instance Type
USINT
0=explicit message
3
Get
Transport Class Trigger
Byte
0x83
4
Get
Produced Connection ID
UINT
11101xxxxxx
xxxxxx=node address
5
Get
Consumed Connection ID
UINT
11110xxxxxx
xxxxxx=node address
6
Get
Initial Comm
Characteristics
Byte
0x33
7
Get
Produced Connection Size
UINT
0x80
8
Get
Consumed Connection Size
UINT
0x80
9
Get/Set
Expected Packet Rate
UINT
2500 msect
12
Get
Watchdog Timeout Action
USINT
1=auto delete
13
Get
Produced Connection Path
Length
UINT
6
14
Get
Produced Connection Path:
LogicalSegment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Array of:
USINT
0x20
0x04
0x24
4, 6, 8, 10-19, 21, 22,
24-28, 30, 31, 33, 34, 36,
37, 39-49 (multiple
instances supported)
0x30
0x03
15
Get
Consumed Connection
Path Length
UINT
6