Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual
Page 124
Publication 1403-IN054B-EN-P - August 2001
B-94 DeviceNet Data Tables
Instance 4 Attributes (Predefined Master/Slave COS/Cyclic
Message Connection)
16
Get
Consumed Connection
Path:
Logical Segment,Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Array of:
USINT
0x20
0x04
0x24
3, 5, 7, 9, 20, 23, 29, 32,
35, 38 (multiple instances
supported)
0x30
0x03
17
Get
Production Inhibit Time
UINT
0
Attribute ID
Access Rule
Name
DeviceNet
Data Value
Attribute ID
Access Rule
Name
DeviceNet
Data Value
1
Get
State
USINT
0=nonexistent
1=configuring (default)
2=waiting for connection
ID 3=established 4=timed
out 5=deferred delete
2
Get
Instance Type
USINT
1=I/O message
3
Get
Transport Class Trigger
Byte
0x02, 0x03, 0x12, 0x13,
0x00 or 0x10 (valid
choices)
4
Get
Produced Connection ID
UINT
10xxxxxx010
xxxxxx=node address
or 0xFFFF
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx=node address
6
Get
Initial Comm
Characteristics
Byte
0x01 or 0x0f
7
Get
Produced Connection Size
UINT
8
8
Get
Consumed Connection Size
UINT
0
9
Get/Set
Expected Packet Rate
UINT
0 ms
12
Get
Watchdog Timeout Action
USINT
0=timeout (default)
13
Get
Produced Connection Path
Length
UINT
6
14
Get
Produced Connection Path
LogicalSegment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number
Array of:
USINT
0x20
0x04
0x24
0x01
0x30
0x03
15
Get
Consumed Connection
Path Length
UINT
4 or 0