B-94 DeviceNet Data Tables

Instance 4 Attributes (Predefined Master/Slave COS/Cyclic
Message Connection)

16

Get

Consumed Connection
Path:
Logical Segment,Class
Class Number
Logical Segment, Instance
Instance Number

Logical Segment, Attribute
Attribute Number

Array of:
USINT

0x20
0x04
0x24
3, 5, 7, 9, 20, 23, 29, 32,
35, 38 (multiple instances
supported)
0x30
0x03

17

Get

Production Inhibit Time

UINT

0

Attribute ID

Access Rule

Name

DeviceNet

Data Value

Attribute ID

Access Rule

Name

DeviceNet

Data Value

1

Get

State

USINT

0=nonexistent
1=configuring (default)
2=waiting for connection
ID 3=established 4=timed
out 5=deferred delete

2

Get

Instance Type

USINT

1=I/O message

3

Get

Transport Class Trigger

Byte

0x02, 0x03, 0x12, 0x13,
0x00 or 0x10 (valid
choices)

4

Get

Produced Connection ID

UINT

10xxxxxx010
xxxxxx=node address
or 0xFFFF

5

Get

Consumed Connection ID

UINT

10xxxxxx101
xxxxxx=node address

6

Get

Initial Comm
Characteristics

Byte

0x01 or 0x0f

7

Get

Produced Connection Size

UINT

8

8

Get

Consumed Connection Size

UINT

0

9

Get/Set

Expected Packet Rate

UINT

0 ms

12

Get

Watchdog Timeout Action

USINT

0=timeout (default)

13

Get

Produced Connection Path
Length

UINT

6

14

Get

Produced Connection Path
LogicalSegment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number

Array of:
USINT

0x20
0x04
0x24
0x01
0x30
0x03

15

Get

Consumed Connection
Path Length

UINT

4 or 0