7-6
Troubleshooting
The module maintains an event queue that reports the history of its
actions. You can view the event queue using DriveExplorer (4.03 or
higher) or DriveExecutive (3.01 or higher) software.
Events
Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
Viewing and Clearing Events
Code
Event
Description
1
No Event
Empty event queue entry.
2
SCANport
Bus Off Flt
A bus-off condition was detected on SCANport. This event may
be caused by loose or broken cables or by noise.
3
Ping Time Flt A ping message was not received on SCANport within the
specified time.
4
Port ID Flt
The module is not connected to a correct port on a SCANport
product.
5
Port Change
Flt
The SCANport port changed.
6
Host Sent
Reset
The drive sent a reset event message.
7
EEPROM
Sum Flt
The EEPROM in the module is corrupt.
8
Online @
125kbps
The module detected that the drive is communicating at 125
kbps.
9
Reserved
Not used.
10
Bad Host Flt
The module was connected to an incompatible product.
11
Reserved
Not used.
12
Type 2 Login
The module has logged in for type 2 control.
13
Type 2 Time
Flt
The module has not received a type 2 status message within the
specified time.
14
DL Login
The module has logged into a Datalink.
15
DL Reject Flt The drive rejected an attempt to log in to a Datalink because the
Datalink is not supported or is used by another peripheral.
16
DL Time Flt
The module has not received a Datalink message within the
specified time.
17
Reserved
Not used.
18
Reserved
Not used.
19
Reserved
Not used.
20
Reserved
Not used.
21
Reserved
Not used.
22
App Updated Startup sequence detected new application firmware.