Module parameters b-5 – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual
Page 105

Module Parameters
B-5
32
[SP I/O Cfg]
Sets the I/O that is transferred through the module.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required:
Yes
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
33
[SP I/O Act]
Displays the I/O that the module is actively
transmitting. The value of this parameter will
usually be equal to the value of Parameter 32 - [SP
I/O Cfg]. If not, reset the EN1 or see
.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read Only
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
34
[Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if any of the following is true:
• Parameter 30 - [Comm Flt Action] is set to
“Send Flt Cfg” and communications are
disrupted.
• Parameter 31 - [Idle Flt Action] is set to “Send
Flt Cfg” and the scanner is idle.
• Parameter 51 - [Peer Flt Action] is set to “Send
Flt Cfg” and communications are disrupted.
The bit definitions will depend on the product to
which the module is connected.
Default:
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
Type:
Read/Write
Reset Required:
No
35
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
• Parameter 30 - [Comm Flt Action] is set to
“Send Flt Cfg” and communications are
disrupted.
• Parameter 31 - [Idle Flt Action] is set to “Send
Flt Cfg” and the scanner is idle.
• Parameter 51- [Peer Flt Action] is set to “Send
Flt Cfg” and communications are disrupted.
Default:
0
Minimum:
-32768
Maximum:
32767
Type:
Read/Write
Reset Required:
No
Parameter
No. Name and Description
Details
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6