Register object, Class code, Instances – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual
Page 116: Class attributes, Class code instances class attributes
C-6
EtherNet/IP Objects
Class Code
Instances
Class Attributes
Register Object
Hexadecimal
Decimal
0x07
7
Instance
Description
1
All I/O data being read from the SCANport product (read-only)
2
All I/O data written to the SCANport product (read/write)
3
Logic Status and Feedback data (read-only)
4
Logic Command and Reference data (read/write)
5
Datalink A (input data from device to scanner) (read only)
6
Datalink A (output data from scanner to device) (read/write)
7
Datalink B (input data from device to scanner) (read only)
8
Datalink B (output data from scanner to device) (read/write)
9
Datalink C (input data from device to scanner) (read only)
10
Datalink C (output data from scanner to device) (read/write)
11
Datalink D (input data from device to scanner) (read only)
12
Datalink D (output data from scanner to device) (read/write)
13
Logic Status and Feedback Data (read-only)
14
Mask
(1)
(read/write)
(1)
The mask command word is set to the value of the first word of the data where
there are ones in the second word of the data. Command = (old command and not
word 2) or (word 1 and word 2). This only controls specified bits in the Logic
Command data to the SCANport product and does not change the Reference
value.
15
Logic Status (read-only)
16
Logic Command (read/write)
17
Feedback (read-only)
18
Reference (read/write)
Attribute
ID
Access
Rule
Name
Data Type
Description
100
Set
Control Timeout
UINT
Control timeout in seconds