To set a module to transmit peer-to-peer data – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual
Page 36
3-10
Configuring the Module
4. Reset the module. See
The module is ready to receive I/O from the master (i.e., scanner). You
must now configure the scanner to recognize and transmit I/O to the
module. Refer to
,
Configuring the Scanner or Bridge
.
To set a module to transmit Peer-to-Peer data
1. Verify that Parameter 61 - [Peer Out Enable] is set to Off. This
parameter must be Off while you configure peer output parameters.
2. Select the source of the data to output to the network in Parameter
59 - [Peer A Output].
3. If desired, select an additional source of the data to output to the
network in Parameter 60 - [Peer B Output].
4. Set Parameters 62 - [Peer Out Time] and 63 - [Peer Out Skip] to
establish the minimum and maximum intervals between Peer
messages. Because the module transmits Peer messages when a
change-of-state condition occurs, minimum and maximum intervals
are required.
–
The minimum interval ensures that the module does not transmit
messages on the network too often, thus minimizing network
traffic. It is set in Parameter 62 - [Peer Out Time]. The default
is 10.00 seconds.
Table 3.F Parameter 61 - [Peer Out Enable] Setup Values
Value Setting
0
Off (Default)
1
On
Table 3.G Parameter 59 - [Peer A Output] Setup Values
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 - 5
Datalink A, B, C, or D Input
6 - 9
Datalink A, B, C, or D Output
Table 3.H Parameter 60 - [Peer B Output] Setup Values
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 - 5
Datalink A, B, C, or D Input
6 - 9
Datalink A, B, C, or D Output