Using I/O Messaging
5-11
Figure 5.5 Example ControlLogix Ladder Logic Program for I/O Messaging (Cont.)
11
Forward_Command
1305
Logic Command
FORWARD
AB1305_Drive:O.Data[0].4
12
/
Forward_Command
1305
Logic Command
REVERSE
AB1305_Drive:O.Data[0].5
This rung provides the Reference word to the 1305 drive. Note that the value is in an engineering unit, where "32,767"
equals the Parameter 19 [Maximum Freq] value and "0" equals 0 Hz. The relationship is linear. For example, if Parameter
19 = 60 Hz (default setting), then:
32,767 = 60 Hz
16,384 = 30 Hz
8,192 = 15 Hz
4,096 = 7.5 Hz
0 = 0 Hz (etc.)
13
Move
Source
Reference
16384
Dest AB1305_Drive:O.Data[1]
16384
MOV
Reference
This rung provides the Reference word to the 1305 drive. Note that the value is in an engineering unit, where "32,767"
equals the Parameter 19 [Maximum Freq] value and "0" equals 0 Hz. The relationship is linear. For example, if Parameter
19 = 60 Hz (default setting), then:
32,767 = 60 Hz
16,384 = 30 Hz
8,192 = 15 Hz
4,096 = 7.5 Hz
0 = 0 Hz (etc.)
Datalink data sent to drive. This rung is used for display purposes only. The AB1305_Drive:O.Data[*] tags could be used
directly elsewhere in the ladder program.
AB1305_Drive:O.Data[2] = Datalink A1 1305 Pr.111 = 7 [Accel Time 1]
AB1305_Drive:O.Data[3] = Datalink A2 1305 Pr.112 = 8 [Decel Time 1]
AB1305_Drive:O.Data[4] = Datalink B1 1305 Pr.113 = 10 [Stop Select]
AB1305_Drive:O.Data[5] = Datalink B2 1305 Pr.114 = 24 [Jog Frequency]
AB1305_Drive:O.Data[6] = Datalink C1 1305 Pr.115 = 27 [Preset Freq 1]
AB1305_Drive:O.Data[7] = Datalink C2 1305 Pr.116 = 28 [Preset Freq 2]
AB1305_Drive:O.Data[8] = Datalink D1 1305 Pr.117 = 29 [Preset Freq 3]
AB1305_Drive:O.Data[9] = Datalink D2 1305 Pr.118 = 73 [Preset Freq 4]
14
Copy File
Source
Datalinks_to_Drive[0]
Dest AB1305_Drive:O.Data[2]
Length
8
COP
Datalink A1
Datalink data sent to drive. This rung is used for display purposes only. The AB1305_Drive:O.Data[*] tags could be used
directly elsewhere in the ladder program.
AB1305_Drive:O.Data[2] = Datalink A1 1305 Pr.111 = 7 [Accel Time 1]
AB1305_Drive:O.Data[3] = Datalink A2 1305 Pr.112 = 8 [Decel Time 1]
AB1305_Drive:O.Data[4] = Datalink B1 1305 Pr.113 = 10 [Stop Select]
AB1305_Drive:O.Data[5] = Datalink B2 1305 Pr.114 = 24 [Jog Frequency]
AB1305_Drive:O.Data[6] = Datalink C1 1305 Pr.115 = 27 [Preset Freq 1]
AB1305_Drive:O.Data[7] = Datalink C2 1305 Pr.116 = 28 [Preset Freq 2]
AB1305_Drive:O.Data[8] = Datalink D1 1305 Pr.117 = 29 [Preset Freq 3]
AB1305_Drive:O.Data[9] = Datalink D2 1305 Pr.118 = 73 [Preset Freq 4]