Net a status indicator, Net a status indicator -4 – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual
Page 84

7-4
Troubleshooting
Net A Status Indicator
Status
Cause
Corrective Action
Off
The module is not
powered, the module is not
connected properly to the
network, or the module
needs an IP address.
• Securely connect the module to the drive using a
1202-Cxx Communication cable.
• Securely connect the Ethernet cable to the Ethernet
connector.
• Set a unique IP address using a BOOTP server or
by disabling BOOTP and using parameters.
• Apply power to the drive and module.
Solid Red
The module failed
duplicated IP address
detection test.
Configure the module to use a unique IP address and
cycle power.
Flashing Red
An EtherNet/IP connection
has timed out.
• Place the controller in RUN mode, or apply power to
the peer device that will send I/O.
• Check the amount of traffic on the network.
Flashing Red/
Green
The module is performing
a self-test.
No action required.
Flashing Green The module is properly
connected but is not
communicating with any
devices on the network.
• Place the controller in RUN mode, or apply power to
the peer device that will send I/O.
• Program a controller or peer device to recognize
and transmit I/O or make a messaging connection to
the module.
• Configure the module for the program in the
controller or the I/O from the peer device.
Solid Green
The module is properly
connected and
communicating on the
network.
No action required.