Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual
Page 108

B-8
Module Parameters
51
[Peer Flt Action]
Sets the action that the module and drive take if
the module detects that the Ethernet/IP
communications with a peer have been disrupted.
This setting is effective only if I/O is transmitted
through the module.
Default:
0 = Fault
Values:
0 = Fault
1 = Zero Data
2 = Hold Last
3 = Send Flt Cfg
Type:
Read/Write
Reset Required:
No
52
53
54
55
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]
Sets the bytes in the IP address that specifies the
device from which the module receives
(consumes) Peer I/O data.
Important: The Peer Inp Addr must be on the
same subnet as the 1203-EN1 module. See “IP
Addresses” in the
for more information.
Changes to these parameters are ignored when
Parameter 57 - [Peer Inp Enable] is On.
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required:
No
56
[Peer Inp Timeout]
Configures the time-out for a peer connection. If
the time is reached without the module receiving
(consuming) a message, the module will respond
with the action specified in Parameter 51 - [Peer
Flt Action].
In a module receiving (consuming) Peer I/O, the
value of this parameter must be greater than the
product of the value of Parameter 62 - [Peer Out
Time] in the module transmitting (producing) Peer
I/O multiplied by the value of Parameter 63 - [Peer
Out Skip] in the module transmitting (producing)
Peer I/O.
Default:
10.00 Seconds
Minimum:
0.01 Seconds
Maximum:
10.00 Seconds
Type:
Read/Write
Reset Required:
No
Parameter
No. Name and Description
Details
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 51 - [Peer Flt
Action] lets you determine the action of the module and connected drive if the
module is unable to communicate with the designated peer. By default, this
parameter faults the drive. You can set this parameter so that the drive continues to
run. Precautions should be taken to ensure that the setting of this parameter does
not create a risk of injury or equipment damage. When commissioning the drive,
verify that your system responds correctly to various situations (for example, a
disconnected cable).
255 . 255 . 255 . 255
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]