Xtra-guard® 1 – Northern Connectors Alpha Wire XTRA-GUARD Performance Cable User Manual
Page 28

Alpha Wire | www.alphawire.com | 1-800-52 ALPHA
Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.
56
Cable > Xtra-Guard > Xtra-Guard 1 > Multipair > Supra-Shield Foil/Braid > 300 V
Xtra-Guard® 1
High Performance
300 V Supra-Shield® Foil/Braid, Multipair
UL CM
UL AWM 2343 VW-1
CSA CMG FT4
Operating Temperature
• –30°C to +80°C (AWM)
• –30°C to +105°C (CM)
Conductor Color Coding
• Chart E (page 520)
• Jacket Colors
• Put-ups: slate
• Bulk: nine colors available
(page 31, minimums
may apply)
Materials
• Stranded tinned copper
conductors
• Premium PVC insulation
• Supra-Shield foil + braid shield:
Aluminum/polyester/aluminum
foil with 25% overlap min.
Tinned copper drain wire sized
the same as conductors
Tinned copper braid, 70%
coverage min.
• Nylon ripcord
• Premium PVC jacket
• UV resistant
Availability
100 ft (30.5 m)
500 ft (152 m)
1000 ft (305 m)
Bulk, cut to length
FIT® Tubing Recommendations
• FIT-221: General-purpose,
cross-linked polyolefin (indoor)
• FIT-321: Medium-wall,
adhesive-lined, cross-linked
polyolefin (outdoor)
24 AWG (0.23 mm
2
)
Stranding: 7/32 (7 x 0.20 mm)
Insulation thickness: 0.010 (0.25 mm)
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
5330C
5
0.354
8.99
0.063
1.60
5331C
7
0.376
9.55
0.063
1.60
5332C
12
0.458
11.63
0.063
1.60
5333C
15
0.491
12.47
0.063
1.60
5334C
19
0.519
13.18
0.063
1.60
5335C
27
0.602
15.29
0.063
1.60
5336C
37
0.669
16.99
0.063
1.60
22 AWG (0.35 mm
2
)
Stranding: 7/30 (7 x 0.25 mm)
Insulation thickness: 0.010 (0.25 mm)
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
5340/2C
2
0.322
8.18
0.063
1.60
5340C
5
0.381
9.68
0.063
1.60
5341C
7
0.406
10.31
0.063
1.60
5342C
12
0.499
12.67
0.063
1.60
5344C
19
0.569
14.45
0.063
1.60
5345C
27
0.669
16.99
0.063
1.60
5346C
37
0.738
18.75
0.063
1.60
20 AWG (0.56 mm
2
)
Stranding: 7/28 (7 x 0.32 mm)
Insulation thickness: 0.010 (0.25 mm)
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
5350/4C
4
0.388
9.86
0.063
1.60
5350C
5
0.416
10.57
0.063
1.60
5351C
7
0.446
11.33
0.063
1.60
5351/9C
9
0.505
12.83
0.063
1.60
5353C
15
0.597
15.16
0.063
1.60
5354C
19
0.634
16.10
0.063
1.60
5355C
27
0.749
19.02
0.063
1.60