Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 9.0 EN · 12/2013 · TD17

43

6

Commissioning

6.4

Setting the IP configuration

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.4.3

Setting via Siemens »STEP7« (»HW Konfig«)

How to allocate the IP address via »STEP7« (»HW Konfig«):

1. Create a »STEP7« project with an IO Controller.

If the Siemens »HW Konfig« software is used for creating an IO Controller, you are

automatically prompted to allocate an IP address for the IO Controller.
For this purpose, the IO controller and the communication module must be connected to

the PROFINET network and an online connection between your PC and the IO controller

must be established.
In our example, IP address 172.31.200.11 has been allocated to the IO controller.

Note!

• Changes become effective immediately and are saved with mains failure protection.
• When the IO Controller is connected to the network, the IP address – which has been

allocated in the Siemens »HW Konfig« – is set automatically by the IO Controller in

the communication module when the network starts up.