beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 81

background image

14.1

95-8533

4-4

Moving within the Main Menu is done by using the

NEXT or PREVIOUS pushbuttons located on the

controller’s front panel. The menu options will scroll

upward (NEXT Pushbutton) or downward (Previous

Pushbutton) while the Main Menu name remains

stationary. When the desired menu option is selected

by the “>” indicator, the ENTER pushbutton is pressed

to advance the menu display to the desired

information set.

Note

Pressing the CANCeL pushbutton from within
any sub-menu returns the display to the Main
Menu. the display will also return to the Main
Menu if left unattended for a period of 20
minutes. If an alarm or trouble condition is
present after 20 minutes, the display will change
to the existing Alarm or trouble message.

DISPLAY ALARMS

displays a list of existing Alarms

and Trouble conditions. Moving within this menu is

done by using the NEXT or PREVIOUS pushbuttons.

Note

Multiple alarm information can be viewed by
pressing the NeXt or PReVIoUS pushbuttons.
Pressing CANCeL will return the menu to the
DISPLAY ALARMS menu.

DISPLAY DEVICES

displays device information on all

devices on the LON loop. Device tag name, type, and

node address are displayed.

Pressing the NEXT or PREVIOUS pushbuttons allows

cycling through devices. Pressing the CANCEL

pushbutton will return the display to the Main Menu.

DEVICE TAG NAMES

displays device tag name

information for all devices on the LON loop.

Pressing the NEXT or PREVIOUS pushbutton allows

cycling through devices. Pressing the CANCEL

pushbutton will return the display to the Main Menu.

SET TIME AND DATE

provides access to

configuration controls for system clock and date

settings.

Note

When the Set time and Date menu opens, the
current hour will flash.

To move within this menu, press the ENTER

pushbutton until the desired property is flashing. To

set the desired property value, press the NEXT

Pushbutton to increase or PREVIOUS Pushbutton to

decrease the value. When the desired value is

displayed, press the ENTER pushbutton. This will

advance the menu to the next property and it will

flash. When all desired properties have been entered,

press the ENTER pushbutton until the message “Press

ENTER to Save” is displayed. When the ENTER

pushbutton is pressed, the settings are saved and the

menu changes back to the MAIN MENU.

>Display Alarms
Display Devices
Device Tagnames

Main Menu

Tag Name
Alarm Description
Time & Date

ack

Alarm Type

Off/On

Add:63 UV / IR Detect

No Fault

Z398-63 U / I

11:20:52

Set Time & Date

Jul 29 / 2002

Controller

Z398-80 X

Device Tagnames