14.1

95-8533

4-25

DCIO Startup
1. The Power-on LED should be illuminated. The

Fault LED should blink once on power up, then

remain off.

2. The input circuits should indicate the proper state

of the input device (channel active LED illuminates

when the circuit is closed). Check the input

power supply and associated wiring. Verify

proper voltage per the Troubleshooting matrix.

3. The output circuits should indicate the proper

state for the programmed device (channel active

LED illuminates when the circuit is active). Check

the power supply and associated wiring. Verify

proper voltage per the Troubleshooting matrix.

4. The circuits should not indicate a fault condition

(channel fault LED illuminates when the circuit is

in fault). Check the end-of-line devices and

associated wiring. Verify proper voltage per the

Troubleshooting matrix.

5. Test the entire system for proper operation to

ensure that the configuration was performed

properly.

Relay Module Startup
1. The Power-on LED should be illuminated. The

Fault LED should blink once on power up, then

remain off.

2. The output circuits should indicate the proper

state for the programmed device (channel active

LED illuminates when the circuit is active).

3. Test the entire system for proper operation to

ensure that the configuration was performed

properly.

Analog Input Module Startup
1. The Power-on LED should be illuminated. The

Fault LED should blink once on power up, then

remain off.

2. The input circuits should indicate the proper state

for the programmed device (channel active LED

illuminates when the circuit is active).

3. The circuits should not indicate a fault condition

(channel fault LED illuminates when the circuit is

in fault).

4. Test the entire system for proper operation to

ensure that the configuration was performed

properly.

Intelligent Protection Module Startup
1. The Power-on LED should be illuminated. The

Fault LED should blink once on power up, then

remain off.

2. The output circuits should indicate the proper

state for the programmed device (channel active

LED illuminates when the circuit is active).

3. The circuits should not indicate a fault condition

(channel fault LED illuminates when the circuit is

in fault).

4. Test the entire system for proper operation to

ensure that the configuration was performed

properly.