Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual
Page 130
95-8533
A-4
14.1
eQPss suPervising systeM
• National Fire Alarm Code performance verified per ANSI/NFPA 72-2002. Refer to Figures A-2 and B-2 for EQPSS
Supervising System architecture.
• Det-Tronics only to integrate proprietary EQPSS Supervising System per Det-Tronics Procedures 5072 and 5073.
eQP systeM Model 000523-009 & 000523-010
• The System consists of:
1 x EQP2120PS-B Power Supply, primary;
1 x EQ3XXX Controller (000523-009)
2 x EQP2410PS-P Converter, secondary;
0 x EQ3XXX Controller (000523-010)
2 x QUINT–DIODE/40 Redundancy module;
0 x EQ3710AIM Module & 1 x EQ3730EDIO Module (000523-009)
1 x EQ2220GFM Ground Fault Monitor
2 x EQ3710AIM Modules & 2 x EQ3730EDIO Modules (000523-010)
• The System is mounted within 60H x 36W x 16D Stainless Steel (type 316), NRTL labeled NEMA 4X rated
enclosure. The enclosure shall be lockable by key lock or padlock.
• EQP system models 000523-009 & 000523-010 are suitable for Cl I, Div. 2, GRPS A, B, C & D (T4); Cl I, Zone 2,
GRP IIC (T4) Hazardous (Classified) Locations; Tamb = –20°C to +49°C.
• Modifications to enclosure (such as conduit entry holes, windows etc.) are permitted when implemented by the
manufacturer of the enclosure.