Eqp2120ps(-b) power supplies – Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual
Page 121

14.1
95-8533
6-10
EQP2XX0PS(–X) POWER SUPPLIES
INPUT VOLTAGE—
EQP2110PS(-P), EQP2120PS(-B): Auto selectable for
120/220 Vac, –15%, +10%; 60/50 Hz, single phase;
EQP2410PS(-P) Converter: 24 Vdc, –15%, +10%.
INPUT cUrrENT—
EQP2110PS(-P):
3.2 A max @ 120 Vac
1.7 A max @ 220 Vac
EQP2120PS(-B):
6.6 A max @ 120 Vac
3.6 A max @ 220 Vac
EQP2410PS(-P):
15.7 A @ max @ 24 Vdc
OUTPUT VOLTAGE—
24.5 Vdc nominal, 24.5 to 28.0 Vdc.
OUTPUT cUrrENT—
EQP2110PS(-P):
10 A
EQP2120PS(-B):
20 A
EQP2410PS(-P):
10 A
TEmPErATUrE rANGE (all models)—
Operating:
–13°F to +131°F (–25°C to +55°C)
(All Applications)
Storage:
–40°F to +185°F (–40°C to +85°C)
HUmIdITY rANGE—
5 to 95% RH at 25°C, non-condensing.
dImENSIONS—
In Inches (Centimeters)
Width Height Depth
EQP2110PS(-P):
3.35(8.5) 5.2(13.0) 5.0(12.5)
EQP2120PS(-B):
3.54(9) 5.2(13.0) 5.0(12.5)
EQP2410PS(-P):
3.2(8.0) 5.2(13.0) 5.0(12.5)
note
Power supplies are designed for DIn rail or
panel mounting (–B or –P suffix).
cErTIfIcATION—
FM / CSA: Ordinary locations.
USCG:
Refer to Appendix D for details.
REDUNDANCY MODULE QUINT–DIODE/40
TEmPErATUrE rANGE—
Operating:
–13°F to +131°F (–25°C to +55°C)
(All Applications)
Storage:
–40°F to +185°F (–40°C to +85°C).
HUmIdITY rANGE—
5 to 95% RH, non-condensing.
dImENSIONS—
in Inches (Centimeters)
Width
Height
Depth
2.4 (6.2)
4 (10.2)
3.3 (8.4)