beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 52

background image

3-33

14.1

95-8533

The output can be configured for latching,

continuous, supervisory, trouble or timed response.

To ensure adequate operating voltage for the output

device, the maximum wiring length from the power

source to the output device must not exceed the

values shown in Table 3-10 for automatic release

applications. (For solenoids, this wire length includes

both the wiring from the power supply to the EDIO

module and the wiring from the module to the

solenoid.)

Supervised Output for Deluge and Pre-action

To ensure proper operating voltage, the input voltage

to the EDIO must be in the range from 21 to 30 vdc

and the maximum wiring length must not exceed the

values shown in Table 3-11 for deluge and pre-action

applications. Per FM Approval requirements, the

secondary power must provide capacity for a 90 hour

minimum standby operation followed by a minimum of

10 minutes of releasing and alarm operation. The

initiating device circuit(s) for use with the deluge
and pre-action system configuration must use
Class A wiring or be wired in conduit within 20 feet
from the EDIO.

NOTE

In EQP systems with EQP2120PS(–B) Power
Supplies, the secondary power is customer
supplied and must be accepted by the Authority
Having Jurisdiction (AHJ).

CONFIGURATION

Setting EDIO Network Address
One unique network address must be assigned to

each EDIO module. The address is set by the 8

switch DIP assembly on the EDIO module.

When using the switches located on the EDIO

module, the address is binary coded and is the sum

of all switches placed in the “closed” position.

Each discrete point of an EDIO module has a tag

number and a descriptor for unique identification. A

tag number must include zone designation, which will

be shown on the controller's display when the point is

in alarm.

Det-Tronics S

3

Safety System Software is used for

device configuration. The following shows the

minimum software/firmware releases:

Table 3-11—Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Solenoids

Maximum Wire Length in Feet (Meters)

FM Solenoid Group Manufacturer

Model

12 AWG

14 AWG

16 AWG 18 AWG

B

ASCO

T8210A107

183 (56)

115 (35)

72 (22)

46 (14)

D

ASCO

8210G207

314 (96)

198 (60)

124 (38)

78 (24)

E

Skinner

73218BN4UNLVNOC111C2

331 (101)

208 (63)

131 (40)

82 (25)

F

Skinner

73212BN4TNLVNOC322C2

130 (40)

82 (25)

51 (16)

32 (10)

G

Skinner

71395SN2ENJ1NOH111C2

331 (101)

208 (63)

131 (40)

82 (25)

H

Viking

HV-274-0601

180 (55)

110 (34)

70 (21)

45(14)

Controller Firmware

S3

Revision

Version

Version

B

4.28

3.1.0.0

Table 3-10—Maximum Wire Length for Releasing Applications

*Fenwal Solenoid
**Ansul Solenoid

Device

Maximum Wire Length in Feet

12 AWG 14 AWG 16 AWG 18 AWG

890181*

150

100

60

895630*

150

100

60

897494*

190

120

75

570537**

3000

1900

1200

750