Connector P4, Terminals 13 to 24
Terminals A, B & C
Channels 5 to 8 Input / Output Terminals
Refer to individual wiring configurations for terminal

descriptions. Only channel 1 is shown in each

diagram. The information is typical for channels 2-8.

Unsupervised Input

Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-26.

The input to the EDIO consists of one or more normally

open or normally closed switches. An EOL resistor is

not required.

Make no connection to “+ Supply” terminal.

Supervised Input (IDC) Open Circuit Supervision
Connect external system wiring to the appropriate

terminals on the terminal block. For Class B wiring,

see Figure 3-27. For Class A wiring, see Figure 3-28.

Note that two channels are used for one circuit when

using Class A wiring.

The input to the EDIO module consists of one or more

normally open switches, with a 10 K ohm, 1/4 watt

EOL resistor in parallel across the last switch.

Make no connection to “+ Supply” terminal.

Supervised Input Open and Short Circuit Supervision

Connect external system wiring to the appropriate

terminals on the terminal block. For Class B wiring,

see Figure 3-29. For Class A wiring, see Figure 3-30.

Note that two channels are used for one circuit when

using Class A wiring. Both wiring configurations

provide indication of open and short circuit fault.

The input to the EDIO module consists of normally

open switches, with a 10 K ohm, 1/4 watt EOL resistor

in parallel across the return channel, and a 3.3 K ohm,

1/4 watt resistor in series with each switch.

NOTE

If using more than one switch, the first active
condition (switch closed) must be latched. Any
subsequent closed switch will indicate a short
circuit fault condition.

Make no connection to “+ Supply” terminal.

Input — Deluge and Pre-Action

The initiating device circuit(s) for use with the deluge and

pre-action system configuration must use Class A wiring

or be wired within 20 feet and in conduit from the EDIO.

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

EOL

RESISTOR

10 K

C2091

Figure 27—Supervised Input Configuration – Class B

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

EOL

RESISTOR

10 K

INLINE

RESISTOR

3.3 K

C2092

Figure 3-29—Supervised Input Configuration

for Opens and Shorts – Class B

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

+ SUPPLY A

IN– / OUT+ B

COMMON C

4

5

6

B2291

EOL

RESISTOR

10 K

Figure 3-28—Supervised Input Configuration – Class A

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

+ SUPPLY A

IN– / OUT+ B

COMMON C

4

5

6

B2292

INLINE

RESISTOR

3.3 K

EOL

RESISTOR

10 K

Figure 3-30—Supervised Input Configuration

for Opens and Shorts – Class A

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

C2090

Figure 3-26—Unsupervised Input Configuration