beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 67

background image

14.1

3-48

95-8533

CAUTION!

The sensor threads can be coated with an
appropriate grease to ease installation. Also
lubricate the cover threads. (See “Ordering
Information” for part number of recommended
lubricant.)

Connect the external wiring to the appropriate

terminals on the DCU terminal wiring board. Refer to

Figure 3-61 for terminal identification. See Figure 3-62

for an example of a Det-Tronics electrochemical

sensor connected to a DCU.

Attach the communication module to the standoffs as

shown in Figure 3-60. Connect the ribbon cable from

the terminal wiring board to the communication

module.

Set the address for the device. Refer to “Setting

Device Network Addresses” for complete information

regarding the switch setting procedure.

Check the wiring to ensure proper connections, then

pour the conduit seals and allow them to dry (if

conduit is being used).

NOTE

Before placing the cover back on the enclosure
following completion of assembly and wiring,
inspect the enclosure O-ring to be sure that it is
in good condition and properly installed.
Lubricate the O-ring and the threads of the cover
with a thin coat of an appropriate grease to ease
installation. Refer to the “Ordering Information”
section for the part number of the recommended
grease (available from Detector Electronics). If
the installation uses catalytic type combustible
gas sensors, it is imperative that lubricants
containing silicone not be used, since they will
cause irreversible damage to the sensor. Place
the cover on the enclosure. Tighten only until
snug. Do not over tighten.

Sensor Separation for DCU with H2S and O2
Sensors
Since the transmitter for the electrochemical sensor is

already mounted within the sensor housing, simply

mount the entire sensor assembly to the sensor

separation kit junction box and wire it to terminals 2

and 4 inside the DCU, the same as a regular (without

sensor separation) installation. Connect the shield to

the ground terminal in the DCU junction box.

Refer to Table 3-17 for separation distance limitations

for H2S and O2 sensors.

1

2

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1726

Figure 3-61—Wiring Configuration for DCU

1

2

3

4

5

6

7

8

9

10

BLACK

RED

GREEN

DCU

H2S/TOXIC/O2

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1875

Figure 3-62—Electrochemical Sensor Connected to DCU

T0020A

Wire Size

Maximum Wiring Distance

(AWG)

Feet

Meters

18

5700

1750

16

9000

2800

Table 3-17

Maximum Separation Distances — Electrochemical Sensor to DCU