SAFETY MANUAL
PointWatch Eclipse
®
Infrared Hydrocarbon Gas Detector
SIL 2 Certified Model PIRECL
5.1
©
Detector Electronics Corporation 2013
10/13 95-8630
SAFETY CErTiFiED MoDEL PirECL
PoiNTWATCh ECLiPSE ir GAS DETECTor
This manual addresses the specific requirements and
recommendations applicable to the proper installation,
operation, and maintenance of all Safety-Certified
(SIL-Certified) PIRECL Pointwatch Eclipse
®
IR Gas
Detector product versions. For complete information
regarding performance, installation, operation,
maintenance and specifications of the PIRECL, refer
to the PIRECL instruction manual. For information
regarding the PIRECL EQP Model, refer to the EQP
Safety Manual.
SUPPorTiNG DoCUMENTATioN
Description
Document Number
PIRECL Instruction Manual
95-8526
EQP Safety Manual
95-8599
QUALiTY PoLiCY STATEMENT
All quality assurance control measures necessary for
safety management as specified in IEC 61508 Part
1 have been implemented. The quality management
system of Det-Tronics is based on the requirements
of EN ISO 9001 and ANSI/ASQC Q9001 through the
application of the United Technologies Company
Achieving Competitive Excellence (ACE) program. In
addition, the Quality Management System complies
with the European ATEX Directive, EN ISO/IEC 80079-
34, and supervised testing requirements per ISO
17025.
SAFETY MESSAGES
Procedures and instructions in this section may
require special precautions to ensure the safety of
personnel performing the operations. Information that
raises potential safety issues is indicated by the word
“Warning”. Always read and understand these safety
messages.
WARNING
The PIRECL is intended for use in hazardous
environments that may include explosive levels of
flammable gases and vapors. This product must
be properly installed, operated and maintained.
Improper installation or use could result in an
explosion or fire resulting in death or serious
injury.
• Do not remove the transmitter cover in explosive
environments when device power is on and
circuits are live.
• Detector must be properly installed, and wiring
compartment cover must be fully engaged
to meet hazardous area explosion-proof/
non-incendive requirements.