beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 62

background image

3-43

14.1

95-8533

Channels 1 to 3, Terminals 1 to 9
Channels 1 to 3 Inputs

Refer to individual wiring configurations for terminal

descriptions. Only channel 1 is shown in each

diagram. The information is typical for channels 1-3.
Unsupervised Input

Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-52.
The input to the IPM consists of one or more normally

open switches. An EOL resistor is not required.
No connection should be made to “+ Supply”

terminal.

NOTE

Unsupervised inputs are not recommended for
fire alarm applications.

Supervised Input (IDC) Open Circuit Supervision
(Two State – Open and Switch Closure)
Class B
Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-53.
The input to the IPM consists of one or more normally

open switches, with a 10 K ohm, 1/4 watt EOL resistor

in parallel across the last switch.
Make no connection to “+ Supply” terminal.

Supervised Input (IDCSC) Open and Short Circuit
Supervision
(Three state – open, switch closure, and short)
Class B
Connect external system wiring to the appropriate

terminals on the terminal block. See Figure 3-54.
The input to the IPM consists of a normally open

switch, with a 10 K ohm, 1/4 watt EOL resistor in

parallel across the switch, and a 3.3 K ohm, 1/4 watt

resistor in series with the switch.
Make no connection to “+ Supply” terminal.

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

B2090

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

EOL

RESISTOR

10 K

B2091

Figure 3-52—Unsupervised Input Configuration

Figure 3-53—Supervised Input Configuration

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

EOL

RESISTOR

10 K

INLINE

RESISTOR

3.3 K

B2092

Figure 3-54—Supervised Input Configuration (Opens and Shorts)