beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual

Page 56

background image

3-37

14.1

95-8533

Supervised Output for Automatic Release
Supervised Output for Open Circuits
Connect external wiring to the appropriate terminals

on the DCIO terminal block. See Figure 3-43.

Wire one or more releasing devices to the module

output.

NOTE

Make no connection to the “+ Supply” terminal.

The output of the DCIO module supervises the

releasing circuit via the coil of the releasing solenoid.

It is essential to use a releasing device approved for

use with this output module.

NOTE

This type of output does not require the use of
EOL resistors or diodes to supervise the circuit.

The output can be configured for latching, continuous

or timed response.

To ensure proper operating voltage, the maximum

wiring length from the power source to the DCIO

module must not exceed the values shown in Table

3-12 for automatic release applications.

NOTE

For solenoids, this wire length includes both the
wiring from the power supply to the DCIO
module and the wiring from the module to the
solenoid.

Supervised Output for Deluge and Pre-action
Connect external wiring to the appropriate terminals

on the DCIO terminal block. See Figure 3-43.

The output of the DCIO module supervises the

releasing circuit via the coil of the releasing solenoid.

It is essential to use a releasing device approved for

use with this output module.

NOTE

This type of output does not require the use of
EOL resistors or diodes to supervise the circuit.

NOTE

Fo r n ew o r re t ro fi t i n s ta l l a t i o n s , a ny
manufacturer’s non-water based agent release
valves can be wired into the outputs of the ARM
or DCIO modules as long as the devices utilize
24 vdc and do not exceed 2 amperes current
draw.

NOTE

For FM system approval listing, pre-action and
deluge applications require that only FM
approved deluge valves can be wired into the
ARM or DCIO modules. Table 3-13 lists the
supported solenoid groups. Remember that the
valves must utilize 24 vdc and must not exceed
2 amperes current draw.

The output can be configured for latching, continuous

or timed response.

To ensure proper operating voltage, the input voltage

to the DCIO must be in the range from 21 to 30 vdc

and the maximum wiring length must not exceed the

values shown in Table 3-13 for deluge and pre-action

applications. Per FM Approval requirements, the

secondary power must provide capacity for a 90 hour

minimum standby operation followed by a minimum of

10 minutes of releasing and alarm operation. For

initiating device circuit(s) for use with the deluge
and pre-action system configuration, an Enhanced
Discrete Input/Output Module (EDIO) must be
used.

+ SUPPLY A

IN– / OUT+ B

COMMON C

1

2

3

NOTE: SHUNT/FLYBACK DIODES DO NOT NEED

TO BE INSTALLED ON THE FIELD DEVICE.

CIRCUIT PROTECTION IS PROVIDED

WITHIN THE DCIO.

A2323

Figure 3-43—Supervised Output Configuration (Automatic Release)

Table 3-12—Maximum Wire Length for Automatic Releasing

Applications

*Fenwal Solenoid
**Ansul Solenoid

Device

Maximum Wire Length in Feet

12 AWG 14 AWG 16 AWG 18 AWG

890181*

150

100

60

895630*

150

100

60

897494*

190

120

75

570537**

3000

1900

1200

750