14.1

95-8533

NETWORK AND NETWORK

EXTENDER INSTALLATION

Mounting
The device should be securely mounted to a vibration

free surface. (See the “Specifications” section in this

manual for device dimensions.)

Wiring
All devices on the LON are wired in a loop that starts

and ends at the System Controller. To ensure proper

operation, the LON should be wired using high speed

communication grade cable.

NOTE

Cable meeting the specifications listed in Table
3-6 is suitable for distances up to 2000 meters.

Any of the cable types listed in Table 3-7 can be used

for wiring the LON for the distances indicated.

NOTE

If no network extenders are used, the distances
listed are for the entire loop. If network extenders
are used, the distances listed are for the wiring
length between network extenders or between a
network extender and the System Controller.

Table 3-7—LON Maximum Cable Lengths

Note: *Use the same type of cable in each wiring segment

between network extenders.

**Maximum wire lengths represent the linear wire distance of
LON communications wiring between network extenders.

Be sure that selected cable meets all job specifications.

If necessary, consult factory for further suggested cable
types.

***Cables designed to ISA SP50 Type A or IEC 61158-2
Type A are suitable for use in LON/SLC wiring. For armored
version, contact cable manufacturer.

Table 3-6—Typical Specification for 16 AWG (1.5 mm

2

) LON Wiring Cable per Echelon

Minimum Typical Maximum

Units

Condition

DC Resistance, each conductor

14

14.7

15.5

ohm/km

20 C per ASTM D 4566

DC Resistance Unbalanced

5%

20 C per ASTM D 4566

Mutual Capacitance

55.9

nF/km

per ASTM D 4566

Characteristic Impedance

92

100

108

ohm

64 kHz to 1 MHz, per ASTM D 4566

Attenuation

20 kHz

1.3

dB/km

20 C per ASTM D 4566

64 kHz

1.9

78 kHz

2.2

156 kHz

3

256 kHz

4.8

512 kHz

8.1

772 kHz

11.3

1000 kHz

13.7

Propagation Delay

5.6

nsec/m

78 kHz

Length:

6,500 feet/2000 meters maximum (basic loop or between Network Extenders).

Type:

Single twisted pair.

Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.

Cables meeting these specifications are good for up to 2000 meters.

T0049B

Length: 6,500 feet/2000 meters maximum (basic loop or between Network Extenders).
Type: Single twisted pair.
Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.
Cables meeting these specifications are good for up to 2000 meters.

LON Cable

Maximum Length**

(Manufacturer and Part No.)*

Feet

Meters

Belden 3073F (Tray Rated)

6,500

2,000

Det-Tronics NPLFP

6,500

2,000

Technor BFOU

4,900

1,500

Rockbestos Gardex Fieldbus***

1 Shielded Pair, 16 AWG,

Type TC, p/n FB02016-001

6,500

2,000

1 Shielded Pair, 18 AWG,

Type TC, p/n FB02018-001

6,500

2,000