Det-Tronics EQP Fire and Gas Detection/Releasing System User Manual
Page 18

14.1
95-8533
2-12
EQ25xxsam signal audible module
The EQ25xxSAM Series Signal Audible Module (SAM)
(see Figure 2-16) provides two indicating circuits for
controlling UL Listed 24 vdc polarized audible/visual
indicating appliances.
The device is located on the LON and is controlled by
programmable logic in the Controller.
Each output circuit is independently programmable to
allow notification of separate events. Each output can
be individually activated for any one of the following
pre-defined outputs:
1. Continuous
2. 60 beats per minute
3. 120 beats per minute
4. Temporal pattern.
Device outputs operate in the reverse polarity manner
when activated. Each output is rated at 2 amperes.
Auxiliary power input terminals are provided for
additional 24 vdc signaling power where required.
The output circuits are supervised for open and short
circuit conditions. If a wiring fault occurs, a trouble
condition will be indicated at the Controller.
Refer to the EQ25xxSAM Specification Data sheet
(form number 90-1129) for additional information
Figure 2-16—Signal Audible Module
EQ22xxiDC series initiating Device Circuit (iDC)
There are three IDC models available (see Figure 2-17):
The EQ22xxiDC allows discrete inputs from smoke/
heat detectors, manual call stations or other contact
devices.
The IDC accepts two dry contact inputs for use with
devices such as relays, pushbuttons, key switches,
etc. The IDC supports ANSI/NFPA 72 Class B
supervised input circuits
Each circuit requires its own end of line (EOL) resistor
for monitoring circuit continuity. Nominal resistance of
the resistor is 10 k ohms.
The EQ22xxiDCGF Initiating Device Circuit Ground
Fault Monitor (IDCGF) responds to the presence of a
ground fault within the power circuitry of the system.
It provides an unsupervised dry contact input and
ground fault monitoring circuitry for indicating a power
supply trouble condition. It is intended for use with a
third party power supply.
The EQ22xxiDCsC Initiating Device Circuit Short
Circuit (IDCSC) is similar to the IDC, but supports
supervision per EN 54 for European installations.
Refer to the EQ22xxIDC Specification Data sheet
(form number 90-1121) for additional information.
Figure 2-17—Initiating Device Circuit
note
Input types (e.g. fire alarm, trouble, and gas
alarms) are configurable through Det-tronics
Safety System Software (S3).