14.1

95-8533

2-13

EQ22xxDCu and EQ22xxDCuEX
Digital Communication units
The EQ22xxDCU Digital Communication Unit (DCU) is

an analog signal input device that accepts a 4 to 20

milliampere signal. The device is typically connected

to gas detectors, where the analog signal represents

the gas concentration.

Calibration of the DCU involves a non-intrusive

procedure that can be performed by one person at

the device without declassifying the area.

The device supports two alarm setpoints that are

defined as part of the device’s configuration setup.

When detecting combustible gases, the alarm

setpoints represent low and high gas alarm levels.

When detecting oxygen, the alarms represent the

range for the acceptable oxygen level. If oxygen

drops below the alarm range, a low alarm is

generated by the device.

PointWatch/DuctWatch IR gas detector as well as

electrochemical sensors (hydrogen sulfide, carbon

monoxide, chlorine, sulfur dioxide, and nitrogen

dioxide) are examples of devices that can be

connected to the DCU.

note

A catalytic sensor can be connected to a DCU
through a transmitter, which converts the millivolt
signal to a 4 to 20 milliampere signal.

The EQ22xxDCUEX is a specialized version of the

DCU that contains a transmitter for connection to a

Det-Tronics Model CGS catalytic combustible gas

sensor.

Refer to the EQ22xxDCU Specification Data sheet

(form number 90-1118) for additional information.

piRECL pointWatch Eclipse
The Pointwatch Eclipse

®

Model PIRECL is a diffusion-

based, point-type infrared gas detector that provides

continuous monitoring of combustible hydrocarbon

gas concentrations in the range of 0 to 100% LFL.

The LON supervision meets Signaling Line Circuit

(Class X) requirements per NFPA72: 2010 for the

Model PIRECL.

For PIRECL installation, operation, maintenance,

specifications and ordering information, refer to form

number 95-8526.

note

the low alarm range for the eQP PIReCL is
5-40% LFL (the standard PIReCL is 5-60% LFL).

For information regarding USCG Approval of the

PIRECL Detector, refer to Appendix D.

opECL open path Eclipse
The Open Path Eclipse

Model OPECL is an open

path infrared gas detection system that provides

continuous monitoring of combustible hydrocarbon

gas concentrations in the range of 0 to 5 LFL-meters,

over a distance of 5 to 120 meters.

The LON supervision meets Signaling Line Circuit

(Class X) requirements per NFPA72: 2010 for the

Model OPECL.

For OPECL installation, operation, maintenance,

specifications and ordering information, refer to form

number 95-8556.

uD10 DCu Emulator
The FlexVu

®

Model UD10 DCU Emulator (UD10-DCU)

is designed for applications that require a gas detector

with digital readout of detected gas levels. Its LON

interface board makes the UD10-DCU compatible with

Eagle Quantum Premier systems by digitizing the 4-20

mA analog signal from the attached sensor/transmitter

and transmitting the value as a process variable over

the LON to the EQP controller. The UD10-DCU is

designed for use with most currently available

Det-Tronics gas detectors.

For a list of compatible gas detectors, as well as

information regarding installation, operation,

maintenance, specifications and ordering information,

refer to form number 95-8656.