EQ25xxSAM SIGNAL AUDIBLE MODULE
OUTPUT rATING—
2 amperes at 30 vdc maximum.
rESPONSE TImE—
Output relay actuates in <0.1 second after
acknowledging an alarm command message.
SUPErVISOrY cUrrENT—
3.0 ma ± 2.0ma, each circuit.
EOL rESISTOrS —
10 kohm ± 2 kohm. Each circuit must have an EOL
resistor.
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
INPUT cUrrENT (Excluding Output current)—
Standby:
60 ma maximum at 24 vdc.
Alarm:
120 ma maximum at 24 vdc.
STATUS OUTPUT—
Digital communication, transformer isolated (78.5
kbps).
TEmPErATUrE rANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUmIdITY rANGE—
5 to 95% RH, non-condensing.
VIbrATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
dImENSIONS—
See Figure 6-5.
cErTIfIcATION—
FM / CSA:
Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4 ).
Class II/III, Div. 2, Groups F & G (T4).
NEMA/Type 4X.
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
CE:
ATEX/EMC Directive Compliant.
ATEX:
0539
FM
APPROVED
II 2 G
Ex d IIC T4-T6 Gb
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
IP66
Refer to Appendix C for ATEX Approval details.
IEC:
IECEx ULD 10.0010
Ex d IIC T4-T6 Gb
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
Refer to Appendix E for CE Mark details.
EQ24xxNE NETWORK EXTENDER
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
POwEr cONSUmPTION—
2.2 watts nominal at 24 vdc, 2.7 watts maximum.
INPUTS/OUTPUTS—
Digital, transformer isolated (78.5k Baud).
TEmPErATUrE rANGE—
Operating: –40°F to +167°F (–40°C to +75°C)
Storage:
–67°F to +185°F (–55°C to +85°C).
HUmIdITY—
5 to 95% RH at 70°C.
dImENSIONS—
See Figure 6-7.
cErTIfIcATION—
FM / CSA:
Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4 ).
Class II/III, Div. 2, Groups F & G (T4).
NEMA/Type 4X.